TRANSMITTER TR485-103D-150, TR485-
103D-700
Programmable transmitter of temperature, relative humidity
and other derived humidity values with RS485 serial output
Instruction Manual
Vue de la page 0
1 2 3 4 5 6 ... 10 11

Résumé du contenu

Page 1 - Instruction Manual

TRANSMITTER TR485-103D-150, TR485-103D-700 Programmable transmitter of temperature, relative humidity and other derived humidity values with R

Page 2 - Transmitter installation

Not allowed manipulation It is not allowed to operate the device under conditions other than specified in technical parameters. Devices are not design

Page 3 - Dimensions

Appendix A Connection of ELO E06D converter (RS232/RS485) (optionally accessory of the transmitter TR485-103D-700) The ELO E06D converter is an opt

Page 4 - Modbus RTU

2 Instruction Manual for use of temperature and relative humidity transmitter TR485-103D-150, TR485-103D-700 Transmitter is designed for measureme

Page 5 - Jumper and button

It is recommended to use shielded twisted copper cable (e.g. SYKFY ). Outside diameter of the cable must be from 3 to 6.5 mm, maximal length 1200m. Th

Page 6 - Error States of the device

Typical application wiring, connection of terminals Info mode If in doubt of setting of installed transmitter, verification of its address is enabled

Page 7 - Readings on LCD display

5 Sent request and response have syntax: ADDRESS OF DEVICE – FUNCTION – Modbus CRC Supported functions 03 (0x03): Reading of 16-bit registers (

Page 8 - Measuring parameters:

6 115200Bd, parameters of communication link are 1 start bit + eight bit data word (LSB first) + 1 stop bit, without parity. Jumper Jumper is loc

Page 9

7 Error 1 Measured (calculated) value is over upper limit of allowed full scale range. There is a reading „Err1“ on LCD display. Value read fro

Page 10 - End of operation

Technical parameters of the instrument: RS 485 Interface: Receiver-Input Resistance: 96 kΩ Devices on bus: max. 256 (1/8 Unit Receiver Load) Mea

Page 11 - Appendix A

9 The value computed from ambient temperature and relative humidity: Display resolution: 0,1 °